J-XK2080B Field Control Panel Parameters
The J-XK2080B field control panel is specially designed for important places and is suitable for installation at the entrance and exit of fire protection areas such as subways, power plants and mobile complexes.
Each fire extinguishing zone needs to be equipped with a J-XK2080B field control panel. The J-XK2080B field control panel does not need to be registered, and can provide the following signals:
1. Hand automatic state output signal (passive contact signal);
2. Linkage status output signal (passive contact signal);
3. sound and light alarm output signal (active 24V output signal);
4. deflation indicator output signal (active 24V output signal);
5. linkage output signal (active 24V output signal);
6. the main discharge solenoid valve drive signal (active 24V output signal);
7. Continue to release the solenoid valve drive signal (active 24V output signal);
8. Main discharge pressure switch action output signal (passive contact signal);
9. Continue to release the pressure switch action output signal (passive contact signal);
10. Receiving a main discharge pressure switch state signal or its corresponding feedback signal (passive contact signal);
11. Receiving a continuous release pressure switch state signal or its corresponding feedback signal (passive contact signal);
12. receiving the start and stop signal of the start and stop button (passive contact signal);
13. Receive the status signal of the automatic switch of the hand (passive contact signal);
14. Receive the discharge/disable switch signal (passive contact signal).
Specification
1. Dimensions: 380mm × 120mm × 260mm (L*W*H)
2. communication bus voltage: DC18 ~ 30V
3. power control bus voltage: DC5V (static), DC24V (action) maximum drive current: 1A
4. working voltage: normal DC22 ~ 28V output voltage: power supply voltage DC24V ± 0.5V
5. the input signal: the request is a passive contact signal
6. Output signal: There are five sets of active output signals and four sets of passive contact output signals.
The active output signals are: sound and light, deflation lamp, linkage output: the maximum output power is not greater than 24V1A;
Main discharge solenoid valve drive: maximum output power is not greater than 24V2A;
Continuous release solenoid valve drive: maximum output power is not greater than 24V2A;
Besqo Marine offers a wide range of Fire Alarm System. For more information , leave message or send an email to sales@besqo.com.