News
J-XK2080A Field Control Panel Introduction
The J-XK2080A field control panel is a local control panel specially designed for important places.
The J-XK2080A field control panel is generally installed at the entrance and exit of fire protection areas such as subways, power plants and mobile complexes.
A minimum of one J-XK2080A field control panel is required for each fire extinguishing zone. The J-XK2080A field control panel does not need to be registered and can provide the following signals:
1. Hand automatic state output signal (passive contact signal);
2. Linkage status output signal (passive contact signal);
3. sound and light alarm output signal (active output voltage signal);
4. deflation indicator output signal (active output voltage signal);
5. solenoid valve output signal (active output voltage signal);
6. linkage output signal (active output voltage signal);
7. Receiving the start and stop signal of the start and stop button (passive contact signal);
8. Receive the status signal of the hand automatic switch (passive contact signal);
9. Receive the discharge/disable switch signal (passive contact signal);
10. Receive the action signal of the pressure switch or its corresponding feedback signal (passive contact signal).
Specification:
1, communication bus voltage: DC18 ~ 30V
2, power drive bus voltage: DC5V (static), DC24V (action) maximum drive current: <1A
3, power supply voltage: normal DC22 ~ 28V
When equipped with DC-DC power supply (optional): Input voltage: 40 ~ 56V Output voltage: 24V ± 0.5V (connected to the control board) The output is connected to the control board, and the input is connected to the 9508D gas fire control panel.
4. Input signal: required as passive contact signal
5. Output signal: There are four sets of active output signals and three sets of passive contact output signals.
Active output signals are: OUT1 (acoustic light, deflation lamp, linkage output) maximum output power is not greater than 24V1A; OUT2 (solenoid valve) maximum output power is not greater than 24V2A;
The passive contact output signals are: hand automatic state contact signal, pressure switch contact signal, and linkage state output contact signal.
6, the ambient temperature: -10 ~ +50 ° C
7, relative humidity: <95% (40 ° C)
8. Dimensions: 260mm × 100mm × 360mm (L*W*H)
Besqo Marine offers a wide range of Fire Alarm System. For more information , leave message or send an email to sales@besqo.com.