News
JB-MG-J4100 Gas Fire Extinguishing System Control Panel Parameters
Product Name: JB-MG-J4100 Gas Fire Extinguishing System Control Panel
JB-MG-J4100 Gas Fire Extinguishing System Control Panel meets the national mandatory product standard GB16669-2010 "General Technical Conditions for Carbon Dioxide Fire Extinguishing Systems and Components", GB16670-2006 "Cabinet Gas Fire Extinguishing Device" specified standard GA61-2010 "General Technical Conditions for Driving and Control Devices for Fixed Fire Extinguishing Systems" Required performance.
1. the overall structure uses a wall structure
2. Dimensions: 360mm*530mm*120mm (L*W*H)
3. the main power supply: AC170V ~ 265V, 50Hz
4. backup power supply: DC24V, 7Ah
5. control signal line loop resistance ≤ 40Ω, the total length is not more than 1200 meters
6. control power line loop resistance ≤ 4Ω (load 1A)
7. power consumption: ≤ 120 W
8. fire extinguishing area: 1 ~ 8
Each fire extinguishing area can be equipped with 2 to 6 J-XK2080 field control units according to the general mode. Among them, No.1 and No.2 are exempt from registration, and have the basic functions necessary for each fire extinguishing area. No.3~6 are expansion units for expansion. Linkage control must be registered to work properly.
Each fire extinguishing area can be equipped with a J-XK2080A field control panel and 0~4 J-XK2080 field control units according to the subway mode.
The J-XK2080A field control panel does not need to be registered, and has various basic functions necessary for each fire extinguishing area. It includes various signals such as output hand automatic state, linkage state, pressure switch action state, etc. A total of 4 field control units from 3 to 6 are expansion units, which are used to expand linkage control and must be registered for normal operation.
Besqo Marine offers a wide range of Fire Alarm System. For more information , leave message or send an email to sales@besqo.com.