News
DHB-SY-J7610 Residual Current Type Electric Fire Monitoring Detector Parameters
Product Name: DHB-SY-J7610 Residual Current Type Electric Fire Monitoring Detector
Product Features
The current type electrical fire monitoring detector is a stand-alone intelligent detector. Real-time residual current display, 100 mA ~ 900mA preset leakage alarm value.
Automatic diagnosis of faults, with sound and light alarm function, 2 passive output ports, with 485 interface, can communicate with the monitoring equipment network, high alarm accuracy, reliability, simple and practical, easy to install and other functions.
The Scope Of Application
DHB-SY-J7610 Residual Current Type Electric Fire Monitoring Detector is suitable for use in complex facilities such as factories, large warehouses, offices, commercial buildings, hotels, residential and entertainment venues where electrical fires are most likely to occur.
1, the power unit
Mainly composed of fuses, filters, power transformers, full-wave rectifier circuits and voltage regulator circuits.
2, the host unit
It consists of single chip microcomputer, data memory, loop interface circuit and multi-machine communication interface circuit.
3, the display unit
It consists of loop setting circuit, button input circuit, display drive circuit, indicator display circuit, digital tube display circuit and alarm circuit.
Technical indicators
1. This product meets the standard
GB14287 "Electrical Fire Monitoring System Part 2, Residual Current Electrical Fire Monitoring Detector"
2, working power
AC220V
3, the ambient temperature
0°C-55°C
4, the environment humidity
<95%
5, altitude
<2000 meters
6, the size
155mm*110mm*60mm (L×W×H) rail mounting
7, probe capacity
Each detector is equipped with 1 to 8 probes.